Battery Bank Sizing Reference Guide | PES Supply
Static reference tables for battery bank sizing — daily kWh consumption → backup hours → required usable kWh , with matched SKU recommendations from the PES Supply direct-distributor lineup. LFP defaults to 80 % DoD, NMC to 90 %, AGM to 50 %.
Static reference tables for battery bank sizing — daily kWh consumption → backup hours → required usable kWh, with matched SKU recommendations from the PES Supply direct-distributor lineup. LFP defaults to 80 % DoD, NMC to 90 %, AGM to 50 %. For the interactive calculator that includes contractor pricing and inverter compatibility, use the PES contractor portal.
A battery bank sizing pass takes four inputs:
- Daily kWh consumption — the average energy the site uses per day. Pull from a utility bill (monthly kWh / 30). Typical US residence: 25–35 kWh/day.
- Backup hours needed — how many hours of that daily load the battery must cover during an outage. 8 hours (overnight), 24 hours (one full day), 72 hours (multi-day event).
- Depth of discharge — the fraction of nameplate capacity you'll regularly cycle. LFP: 80 %. NMC: 90 %. AGM: 50 %.
- Voltage architecture — 48 V low-voltage or 200–500 V high-voltage. Drives which brands are compatible.
The core equation
Required nameplate kWh = (Daily kWh × Backup hours / 24) ÷ DoD
Example: 30 kWh/day, 24 hours backup, 80 % LFP DoD → (30 × 24/24) / 0.80 = 37.5 kWh nameplate.
| Chemistry | DoD default | Rationale | Brands (PES stock) |
|---|---|---|---|
| LFP | 80 % | Standard warranty envelope. Some brands (BYD, LG) publish 90 %+. | Fortress, EG4, SimpliPhi, Pytes, Enphase, BYD LV, Sonnen, Discover |
| LFP (extended) | 90 % | Enphase IQ, BYD HVL, and select brands warrant deeper cycling | Enphase IQ Battery, BYD Battery-Box HVL/HVM |
| NMC | 90 % | Higher DoD tolerance offsets shorter cycle life | Tesla Powerwall 2 (not stocked) |
| AGM | 50 % | Deeper discharge shortens cycle life dramatically | Sun Xtender, Crown |
Table A — Required nameplate kWh (LFP, 80 % DoD)
| Daily kWh | 8h backup | 24h backup | 72h backup |
|---|---|---|---|
| 5 kWh/day | 2.1 kWh | 6.3 kWh | 18.8 kWh |
| 10 kWh/day | 4.2 kWh | 12.5 kWh | 37.5 kWh |
| 15 kWh/day | 6.3 kWh | 18.8 kWh | 56.3 kWh |
| 20 kWh/day | 8.3 kWh | 25.0 kWh | 75.0 kWh |
| 25 kWh/day | 10.4 kWh | 31.3 kWh | 93.8 kWh |
| 30 kWh/day | 12.5 kWh | 37.5 kWh | 112.5 kWh |
| 40 kWh/day | 16.7 kWh | 50.0 kWh | 150.0 kWh |
| 50 kWh/day | 20.8 kWh | 62.5 kWh | 187.5 kWh |
Table B — Required nameplate kWh (AGM, 50 % DoD)
| Daily kWh | 8h backup | 24h backup |
|---|---|---|
| 5 kWh/day | 3.3 kWh | 10.0 kWh |
| 10 kWh/day | 6.7 kWh | 20.0 kWh |
| 15 kWh/day | 10.0 kWh | 30.0 kWh |
| 20 kWh/day | 13.3 kWh | 40.0 kWh |
| Nameplate range | Matched PES SKUs | Typical use case |
|---|---|---|
| 4–6 kWh | Enphase IQ 5P Kit (5 kWh) · SimpliPhi PHI 3.8 pair | Essential-loads backup, small home 8h coverage |
| 7–10 kWh | SimpliPhi ExprESS 7.6 · Enphase IQ 10T (10 kWh) | Essential-loads whole-home, 10 kWh/day for 24h |
| 10–15 kWh | EG4 PowerPro WallMount 14.3 · Fortress Avalon HV Pro 14.7 | Whole-home essential loads, 20 kWh/day for 12–16h |
| 15–20 kWh | Fortress eVault Max 18.5 · Fortress HV Pro 19.6 | Whole-home resilience, 25 kWh/day 24h |
| 20–30 kWh | Fortress HV Pro 24.5 · SimpliPhi AccESS 22.8 · sonnenCore+ + 10 kWh ×2 | Whole-home + EV charging, 30–40 kWh/day 24h |
| 30–50 kWh | Fortress Avalon HV Pro paralleled · BYD Battery-Box HVL stack · Enphase IQ 10T ×3–4 | Whole-home + EV + shop, 3-day resilience for 15–20 kWh/day loads |
| 50–100 kWh | BYD Battery-Box HVM stack · Fortress HV Pro Business 60 · SimpliPhi AccESS paralleled | Light C&I, 72h resilience on medium loads |
| 100–500 kWh | Fortress HV Pro Business paralleled cabinets · BYD HVM multi-stack | C&I peak shaving + resiliency — see C&I sizing guide |
Scenario 1 — Essential-loads backup (10 kWh/day for 24h)
Required nameplate: 12.5 kWh LFP.
Best-fit SKUs:
- AC-coupled retrofit: Enphase IQ 5P × 3 = 15 kWh, 15-year warranty
- DC-coupled new build: EG4 PowerPro WallMount 14.3, 48 V, ~$3,125
- Pre-wired cabinet: SimpliPhi ExprESS 7.6 ×2
Scenario 2 — Whole-home resilience (25 kWh/day for 24h)
Required nameplate: 31.3 kWh LFP.
Best-fit SKUs:
- Single UL 9540 system: Fortress Avalon HV Pro 24.5 + smart energy panel + 200 A transfer switch
- Value build: EG4 PowerPro WallMount 14.3 × 3 = 34.2 kWh nameplate
- Long-warranty build: Enphase IQ 10T × 3 = 30 kWh usable, 15-year warranty
Scenario 3 — Off-grid with generator backup (40 kWh/day for 8h daily)
Required nameplate: 16.7 kWh LFP.
Best-fit SKUs: SimpliPhi PHI 3.8 × 5 = 17.5 kWh (10,000 cycle life, ideal for daily cycling)
Scenario 4 — Whole-home + EV (35 kWh/day for 24h)
Required nameplate: 43.8 kWh LFP.
Best-fit SKUs: BYD Battery-Box HVL stack (11 kWh × 4 modules ≈ 44 kWh) + SolarEdge Energy Hub inverter, or Fortress HV Pro paralleled cabinets
The kWh sizing pass determines how much battery you need. Voltage architecture determines which battery brand you can use.
| Required kWh | Recommended bus | Reason |
|---|---|---|
| 5–15 kWh | 48 V or AC-coupled | Widest brand compatibility, lowest cost |
| 15–25 kWh | 48 V or HV — either works | HV starts to win on cable cost above 15 kWh |
| 25–40 kWh | HV preferred | Current at 48V exceeds practical bus bar sizing |
| >40 kWh | HV mandatory | Single-stack HV drops copper by 10× |
Site: 2,400 sq ft single-family, PG&E territory, 12 kWh average daily consumption (low-usage household).
Design intent: 24-hour whole-home backup during grid outage, DC-coupled new solar-plus-storage build.
Sizing math: (12 × 24/24) / 0.80 = 15 kWh nameplate required at 80 % LFP DoD.
Voltage: 48 V or HV both work at this size. Choose HV for round-trip efficiency and future EV expansion.
Best-fit SKU: Fortress Avalon HV Pro 14.7 kWh ESS bundle (PES-ESS-BTS-0001, $15,699.99) — 14.7 kWh usable, integrated 7.6 kW hybrid inverter, 200 A transfer switch. Single UL 9540 listing.
Total installed cost: ~$22,000–$26,000 with PV interconnection labor.
Contractor pricing: Register for contractor tier →
How is 'usable' kWh different from 'nameplate' kWh?
Nameplate is the full stored energy in the battery — cell voltage × cell capacity × cell count. Usable is nameplate × depth-of-discharge percentage. LFP at 80 % DoD means a 14.3 kWh nameplate battery has 11.4 kWh usable. NMC at 90 % gives 12.9 kWh usable from the same nameplate. AGM at 50 % gives 7.2 kWh usable. Always size by usable kWh, then divide by DoD to get the nameplate battery you order.
What DoD should I use for sizing?
LFP: 80 % (or 90 % for BYD Premium and select brands). NMC: 90 %. AGM: 50 %. Some brands publish higher usable DoD than 80 % LFP standard — BYD Battery-Box HVL is 96 %, LG Chem RESU is 90 % — but the 80 % LFP default matches most Fortress, EG4, SimpliPhi, and Pytes warranty terms.
Do I need a professional calculator?
For a rough sizing pass, the tables in this guide plus the reference chart cover 90 % of residential and light C&I designs. For a real quote — matched to a specific inverter, matched to a specific load profile, with warranty math and financing lines — use our contractor portal calculator at axis.pesdistribution.com/portal/battery-sizing-calculator. Registered contractors get access free.
How much backup runtime do I need?
For a whole-home essential-loads backup during a grid outage, 8 hours is the practical minimum (covers an overnight outage). 24 hours covers a full-day outage. 72 hours covers a multi-day event (hurricane, wildfire). Beyond 72 hours, generator or hybrid solar-plus-storage-plus-generator is more cost-effective than a bigger battery bank.
How does daily solar production factor in?
If you're grid-tied with solar, your daily production offsets the daily load, and the battery only covers the shortfall — usually just the evening-peak window. Size the battery to the evening load (typically 30–40 % of daily kWh) rather than the full daily kWh. If you're off-grid or islanded, the battery must cover the full daily load plus reserve for cloudy days (usually 2–3× daily kWh).
Where's the interactive calculator?
The interactive battery sizing calculator lives on the PES contractor portal at axis.pesdistribution.com/portal/battery-sizing-calculator. It takes daily kWh consumption, backup hours needed, DoD preference, voltage architecture, and inverter model, then returns matched SKU pricing with contractor tier applied. Free with a contractor portal registration.
The most common sizing error is guessing at daily kWh consumption instead of measuring it. Three ways to get an accurate number:
Method 1 — Utility bill history
Pull the last 12 months of utility bills. Sum the total kWh, divide by 365. This gives an annual average but misses seasonal peaks. For a real sizing pass, use the summer peak month and the winter peak month separately — the ESS has to handle either.
Method 2 — Smart meter data
Most modern residential meters expose 15-minute or 1-hour interval data via a Green Button download or the utility's customer portal. Download 12 months of data, sort by day, and pull the 90th-percentile daily kWh — this is what to size for.
Method 3 — Load profiling with a clamp meter
For new-construction or unmetered scenarios, use a clamp meter on the incoming service. Log 7 days of 15-minute data (weekday and weekend cycles) and extrapolate. Include planned loads (EV charging, heat pump, mini-split) that aren't in the historical data.
Typical daily kWh benchmarks
| Home type | Daily kWh (avg) | Daily kWh (summer peak) |
|---|---|---|
| Small home, no EV, gas heat | 15–20 | 25 |
| Medium home, no EV, mixed | 25–30 | 40 |
| Large home, all-electric | 40–55 | 75 |
| Home + 1 EV (10k mi/yr) | +8–10 | +15 |
| Home + heat pump primary | +10–15 winter | — |
| Off-grid cabin | 3–8 | 15 |
An essential-loads panel captures a subset of the home's circuits — usually refrigerator, sump pump, garage door, some outlets, some lighting, HVAC or mini-split. It's what most residential batteries actually back up during an outage, because sizing a battery to whole-home load is expensive and rarely necessary.
Essential-loads typical scope
- Refrigerator + freezer: 3 kWh/day
- Sump pump (intermittent): 1 kWh/day
- Garage door: negligible
- Wi-Fi router + modem: 0.3 kWh/day
- LED lighting (partial): 1 kWh/day
- Furnace fan (gas heat): 2 kWh/day winter
- Well pump: 2 kWh/day
- Central air conditioning: 15–20 kWh/day summer (usually excluded from essential-loads)
Sum for typical essential-loads scope: 6–10 kWh/day. A 10-14 kWh battery covers 24-hour essential-loads backup easily, which is why the 10-15 kWh residential band is the market sweet spot.
Whole-home sizing
Whole-home backup covers everything on the main service — including central AC or heat pump, EV charging, dryer, oven. This drives daily kWh to 25–55 depending on the season, and the sizing pass yields 20–40 kWh usable for 24-hour coverage. Whole-home is what Fortress Avalon HV Pro 19.6/24.5 and Enphase IQ 10T × 3 are built for.
Most residential LFP batteries parallel in 2–8 unit configurations. Rules of thumb:
- Same-brand only. Cross-brand paralleling breaks the BMS closed-loop protocol.
- Same firmware version. Update all units to the same BMS firmware before commissioning.
- Same state of charge at commissioning. Charge each unit to 50 % SoC on a bench before connecting in parallel.
- Matched cable length between battery and combiner. Unequal cable resistance causes uneven current sharing.
- Individual DC breaker per battery. NEC 706 requires per-unit disconnect for service.
- Per-unit balancing time. On first commissioning, allow 24–48 hours of low-current balancing before full-power discharge.
Practical parallel limits by brand
| Brand | Max parallel units | Total kWh (max) |
|---|---|---|
| Enphase IQ Battery 5P | 8 | 40 kWh |
| Enphase IQ Battery 10T | 4 | 40 kWh |
| Fortress eVault Max 18.5 | 4 | 74 kWh |
| Fortress Avalon HV Pro modules | 5 modules per stack, 2 stacks parallel | 49 kWh |
| EG4 PowerPro WallMount 14.3 | 4 | 57 kWh |
| SimpliPhi PHI 3.8 | 8 | 28 kWh |
| Pytes E-Box 48100R | 8 | 41 kWh |
| BYD Battery-Box HVL modules | 13 modules per stack, 2 stacks parallel | 66 kWh |
Mistake 1 — Sizing to nameplate not usable
Ordering a 14.3 kWh nameplate battery thinking you have 14 kWh usable is a 20 % undersize. Always size on usable × DoD.
Mistake 2 — Ignoring inverter continuous power
A 20 kWh battery paired with a 5 kW inverter can only discharge at 5 kW continuous. Whole-home backup with resistive loads (electric water heater, resistance range) can exceed 8 kW continuous — the inverter is the bottleneck. Size the inverter to peak load, then size the battery to duration × inverter output.
Mistake 3 — Ignoring solar contribution
Grid-tied with 8 kW PV that generates 32 kWh/day changes the sizing math — the battery only has to cover the evening-peak shortfall, not the whole daily consumption. On a self-consumption use case with PV, a 10–15 kWh battery is often plenty.
Mistake 4 — Assuming perfect efficiency
Round-trip efficiency of 96 % means a 15 kWh usable battery only delivers ~14.4 kWh at the AC output during a full discharge. Add 5–8 % headroom to sizing calculations.
Mistake 5 — Ignoring temperature derate
LFP batteries derate charging current below 0 °C. If the install is in an unheated garage in Minnesota, the battery may only accept charge at 0.25C in winter, which cuts effective daily cycling capacity. EG4 AllWeather and Fortress with active heating are the picks for cold-climate installs.
The static tables in this reference guide are enough for a rough sizing pass. Use the interactive calculator when:
- You need matched SKU pricing with contractor tier applied
- You want inverter-battery compatibility validated against the specific hybrid inverter you're spec'ing
- You need to compare 3–5 configurations side-by-side with total installed cost
- You want to model TOU arbitrage or peak shaving against a specific utility rate
- You need a quote-ready line-item breakdown for the customer
The interactive Battery Sizing Calculator lives at axis.pesdistribution.com/portal/battery-sizing-calculator on the PES contractor portal — free with contractor registration.
Battery kWh and inverter kW are two independent sizing decisions. Common combinations:
| Battery nameplate | Recommended inverter kW | Reason |
|---|---|---|
| 5–10 kWh | 3–5 kW | Essential loads, small hybrid inverter sufficient |
| 10–15 kWh | 5–8 kW | Whole-home essential loads, medium hybrid inverter |
| 15–25 kWh | 7.6–12 kW split-phase | Whole-home resilience, split-phase hybrid inverter |
| 25–40 kWh | 12–16 kW | Whole-home + EV, largest single-phase hybrid inverter |
| 40+ kWh | 16 kW + or three-phase | Multi-inverter parallel or three-phase C&I |
Peak vs continuous
Inverters spec two power ratings — continuous and peak. Continuous is what the inverter delivers indefinitely under normal thermal conditions. Peak (surge) is what it delivers for 5–30 seconds to start motor loads. HVAC compressors, well pumps, and refrigerators need surge capacity 2–3× their running load. A 4-ton central AC pulls 4 kW running but 12 kW starting; if your inverter's peak rating is 8 kW, the AC won't start on battery.
Below 0 °C, LFP batteries derate charge acceptance. Below -10 °C, most LFP won't accept charge at all without a self-heating BMS. Cold-climate sizing implications:
- Use a self-heating battery. EG4 PowerPro WallMount AllWeather, Fortress Avalon with cold-weather option, and select SimpliPhi models include self-heating BMS that keeps cells above 0 °C.
- Size up 20 %. Winter kWh consumption in cold-climate homes runs 30–50 % higher than summer averages (electric heat pump, heat strips, longer runtimes). Size to winter peak, not annual average.
- Locate indoors or in a heated garage. Even AllWeather batteries operate more efficiently in mild ambient. Attached garages with basic heating maintain battery performance year-round.
- Increase headroom for solar shortfall. Cloudy winter days with short daylight hours mean the battery discharges deeper and recharges less. Add 30–50 % capacity headroom over the mathematical sizing target.
Above 45 °C ambient, LFP batteries derate power output (charge and discharge). Above 50 °C, most batteries alarm and de-rate to 50 % power. Hot-climate implications:
- Ventilated cabinet or indoor mount. Battery cabinet must maintain internal temperature below 45 °C. Passive vents may not be enough in AZ summers; some C&I installs use active HVAC.
- Avoid direct sun. Wall-mount on north or east-facing walls, or provide shade structure.
- Size larger inverter. Higher summer AC load means the battery discharges harder, and the inverter has to keep up. Size inverter to peak load, not average.
A proper sizing pass yields a documentation package the customer, AHJ, and installer can all work from:
- Load audit — 12 months of utility data with 90th-percentile daily kWh identified.
- Backup scope — essential-loads panel list or whole-home scope defined.
- Battery bank spec — usable kWh, nameplate kWh, chemistry, DoD, brand, model, quantity.
- Inverter spec — continuous kW, peak kW, brand, model, closed-loop battery profile.
- Voltage architecture — 48 V or HV, matched inverter-battery combination.
- UL 9540 listing letter — from the manufacturer, addressed to the AHJ.
- Site plan — cabinet locations, NFPA 855 clearance, service entrance route.
- Installed cost estimate — hardware, labor, permit, interconnection.
- ITC and financing math — post-incentive cost.
- Warranty summary — years, cycles, end-of-warranty capacity, registration process.
The interactive calculator on the PES contractor portal produces items 3, 4, 5, and 8 automatically for any given input load profile — axis.pesdistribution.com/portal/battery-sizing-calculator.
Once the battery is installed and commissioned, verify the sizing was correct with a real-world test:
- Full charge test. Charge the battery to 100 % from utility or PV. Log the total energy in — should match nameplate × charge efficiency (~98 %).
- Full discharge to essential loads. Simulate a grid outage by opening the utility disconnect. Run essential loads on battery only. Log the total energy out and the runtime — should match usable kWh × discharge efficiency.
- Peak load test. Turn on the largest inrush load in the essential-loads scope (AC compressor, well pump start). Verify the inverter delivers the peak surge without tripping.
- Round-trip efficiency. Compute total energy out ÷ total energy in. Should be 90–96 % depending on the brand. Below 88 % suggests a wiring or configuration issue.
- Comms verification. Confirm the inverter reads state of charge from the battery BMS (closed-loop) rather than estimating from terminal voltage. Should update in real time.
The contractor portal calculator at axis.pesdistribution.com/portal/battery-sizing-calculator collects:
- Daily kWh consumption (average) — with an option to upload a Green Button data file for utility-level accuracy
- Backup hours target — 8 / 24 / 72 or custom
- Chemistry preference — LFP / NMC / AGM
- Voltage architecture — 48 V / HV / auto-select
- Existing inverter (if retrofit) — dropdown of Sol-Ark, EG4, Fortress, SolarEdge, Enphase, Victron, Schneider, Outback
- Backup scope — essential-loads / whole-home / off-grid
- Climate zone — cold / moderate / hot for temperature-derate adjustments
- Existing PV kW — for self-consumption offset
The calculator returns:
- Required nameplate kWh
- 3–5 matched SKU configurations with contractor-tier pricing
- Compatibility verified against the specified inverter
- Installed cost estimate
- Post-ITC and financing options
- Line-item quote export (PDF)
Register at axis.pesdistribution.com/portal-registration to access.
For the installer field-reference use case, the fastest path from a homeowner's utility bill to a matched product is:
| Monthly bill kWh | Daily kWh | Whole-home 24h backup requires | Best-fit PES SKU |
|---|---|---|---|
| 300 kWh | 10 kWh | 12.5 kWh nameplate | EG4 PowerPro WallMount 14.3 or Enphase IQ 10T |
| 450 kWh | 15 kWh | 18.75 kWh nameplate | Fortress eVault Max 18.5 or Fortress HV Pro 19.6 |
| 600 kWh | 20 kWh | 25 kWh nameplate | Fortress HV Pro 24.5 or SimpliPhi AccESS 22.8 |
| 900 kWh | 30 kWh | 37.5 kWh nameplate | Fortress HV Pro paralleled or BYD HVL stack |
| 1,200 kWh | 40 kWh | 50 kWh nameplate | BYD HVM stack or Fortress HV Pro Business 60 |
| 1,500 kWh | 50 kWh | 62.5 kWh nameplate | Fortress HV Pro Business 60 or 100 |
| 1,800 kWh | 60 kWh | 75 kWh nameplate | Fortress HV Pro Business 100 or paralleled |
Note this is whole-home 24h backup sizing — if the customer only needs essential-loads backup (which is the more common scope), the required nameplate drops to roughly 30–40 % of the whole-home number, moving the recommended SKU one or two rows up the table.
- DoD (depth of discharge)
- The fraction of nameplate capacity you can cycle without violating warranty. 80 % for standard LFP, 90 % for BYD Premium and Enphase IQ, 50 % for AGM.
- Round-trip efficiency
- Energy out at AC output ÷ energy in at AC input. 90–96 % for typical LFP-plus-hybrid-inverter systems.
- C-rate
- Discharge rate expressed as a fraction of capacity. 0.5C means a battery discharges at half its capacity per hour (a 20 kWh battery at 0.5C discharges 10 kW for 2 hours).
- Nameplate kWh
- The full stored energy in the battery. Sizing target is nameplate × DoD.
- Usable kWh
- What you can actually cycle. Nameplate × DoD.
- Closed-loop
- Battery BMS communicates full state data to the inverter over a proprietary or published protocol. The inverter obeys the battery's operating envelope directly.
- Grid-forming
- Inverter can start loads on battery power without utility present. Required for whole-home backup.
- PTO (Permission to Operate)
- Utility approval to interconnect an ESS or PV system to the grid.
- UL 9540
- North American safety listing for stationary energy storage systems. Required by most AHJs for permitted installation.
Open a Contractor Account
Get trade pricing, freight quotes, and access to the interactive Battery Sizing Calculator on our contractor portal.
Register NowAbout the author: Jennifer Kirstens leads distributor content at PES Supply. Last updated August 2026.